MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Clean cartop
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
Need to clean car top
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Written maintenance control program shall be provided on-site for each elevator.
|
12/19/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
|
|
Need to repair dangling, disconnected loadweighting junction box with exposed wiring on top of car
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
|
|
Repair dangling, disconnected load weighing junction box with exposed wiring on top of car.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
Counterweight buffer is being compressed 2" when car is at a top landing. Shorten suspension ropes to mantain proper counterweight runby.
|
2/18/2022
|