Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintian proper counterweight runby. 2/18/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) x Door operator cover shall be installed. Re-inspection required 2/15/2024
MO Minimum : Elevators (I) - Pits (I)4 x x Counterweight buffer did not return to normal after testing. This is a red tag violation and the unit has been shut down until this is resolved. Re-inspection required 2/15/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency generator testing needs to be performed. Re-inspection required 2/15/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Fire service testing needs to be performed. Re-inspection required 2/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Door operator cover shall be installed
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency generator testing needs to be performed. Re-inspection required