MO Minimum : Elevators
|
(I) - Pits
|
(I)4
|
x
|
x
|
Counterweight buffer did not return to normal after testing. This is a red tag violation and the unit has been shut down until this is resolved. Re-inspection required
|
2/15/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
Counterweight buffer is being compressed 1" when car is at top landing. Shorten suspension ropes to maintian proper counterweight runby.
|
2/18/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Door operator cover shall be installed
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Door operator cover shall be installed. Re-inspection required
|
2/15/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency generator testing needs to be performed. Re-inspection required
|
2/15/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency generator testing needs to be performed. Re-inspection required
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Fire service testing needs to be performed. Re-inspection required
|
2/15/2024
|