Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 9.16 - Ceiling intersection guards 8.6.8.9 Replace anti climbing barricade on outer decking between units at lower end
conversion conversion n/a Bottom demarcation lights don't work 5/1/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(D) Replace broken step tread.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.1.4 Maintenance Records Written maintenance control program shall be provided on-site for each elevator. 12/19/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) x Lower escalator brake torque is only 64 ft lbs. Minimum is 125 ft lbs. Replace escalator brake. Escalator removed from service & red tagged. Re-inspection required before use 2/22/2023
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate A copy of the current state operating certificate shall be on display in the machine room.
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.4 Escalator Combplates Broken comb plate at the bottom shall be replaced 3/29/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x Replace broken step tread. Re-inspection required 3/29/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Unit needs complete cleandown
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.6 Steps x x Most, if not all, step treads have damaged fins on treads, causing sharp edges and excessive gaps between fins. Red-tagged, Re-inspection required 10/2/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks (T)2(A) x x Bottom brake torque is below minimum. Red-tagged, Re-inspection required 10/2/2024
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends Walkoff plate at egress end had missing/broken support braces underneath, need to be replaced
Missouri Minimum : Escalators CSR 40-5.100 State Operating Certificate 5.100(2) display of certificate A copy of the current operating certificate shall be displayed in the machine room 3/29/2024