Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 No No non elev. wiring across top of hoistway needs to be removed also non elev related wiring in machroom needs to be removed 8/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt displayed 8/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt. posted 8/10/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.3.1.1(q) Yes No battery lowering not working 7/11/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4 Instructions for Locating Maintenance Records No No Incomplete MCP need testing procedures for equipment on site 8/7/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No phone not working 8/2/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone dials out but cll ctr. cant tell me my location 7/6/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emg phone not working no dial tone 8/7/2023
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage No No left cyl. has excessive leaking needs to be repacked 8/7/2023
conversion conversion n/a No No Phone not working. 11/1/2018