conversion
|
conversion
|
n/a
|
|
|
needs a set of electrical prints for elevator
|
10/2/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
needs current certificate posted
|
10/2/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. ( tables, mop bucket, etc
|
6/6/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking. Door jams
|
6/6/2023
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
door will not close on phase I when safety edge is blocked--REINSPECT REQUIRED
|
7/9/2018
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
(S)1 (RD)safety edge will not let door go shut no phase I & II
|
6/4/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
If edge is blocked, doors will not shut on phase I
|
7/11/2019
|