Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.7 Cleaning of Hoistways and Pits non elevator items stored in machine room 10/28/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed x Testing incomplete, need to place car on stop ring and verify cam activates top final limit. ( car door drifts open on inspection, not allowing car to run at top) REINSPECTION REQUIRED 7/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x G(1)1.18.1/8.6.4.13.1(l): CAR DOOR RESTRICTOR SHALL WORK AT ALL FLOORS 3/1/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x G(1)/8.6.4.15/1.5.1(b) : EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER 3/1/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 Non-elevator related items shall not be stored in Machine Room. 6/6/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 H(4)/2.5/8.11.2.1.2(e). Non-elevator related items shall not be stored in Machine Room. (Carpet cleaning machine, etc) 6/28/2023