MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
x
|
|
Auxiliary lighting inoperable, repair or replace.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.32 - Control Valve
|
8.11.3.1.2 (o)
|
x
|
|
Car sank 3" during 15 minute standing test. Check valve and control valve are leaking hydraulic fluid back into the tank. Elevator drops and relevels due to defective valve. Repair and/or replace.
|
1/22/2021
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Rear car door restrictor shall work.
|
11/6/2018
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit shall be cleaned of dust and debris. Remove pallet in the pit.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room does not meet code requirements. Provide an ABC type extinguisher of proper size for the room.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The original signage for “In Case of Fire” has been replaced with non-pictograph signage. Reinstall signage that conforms to the building code this elevator was installed to (BOCA 1993 edition).
|
|