Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Provide protection on in car light bulbs, such as plastic tube to prevent breakage. 6/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Replace missing "In Case of Fire Do Not Use Elevators" signage at P1 and main lobby levels. 6/1/2021
MO Minimum : Elevators (I) - Pits (I)1 Elevator pit is full of water and shall be pumped out
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x x Phase II fire service shall be made operable, this is a red tag violation 4/28/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is incomplete, need to perform the following test to complete inspection: Counterweight buffer shall be tested, could not perform testing due to water in the pit. Re-inspection required