Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) 1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1) 11/8/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.2 Callbacks (Trouble Calls) Documentation 2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2 11/8/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x While on car top inspect,running down and releasing buttons,car continues down. Repair as needed. 8/2/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Upon activating Phase I key switch, car intermittently would close doors. Repair as needed. 8/2/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase II was working intermittently, repair as needed. 8/2/2022