MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
1. Elevators with fire service features shall comply with the edition of ASME A17.1 that the elevator was constructed to meet. If the smoke detector at the designated level is activated, the elevator should return to an alternate level designated by the enforcing authorities.
|
12/14/2018
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
1) Where valves and cylinders use packing glands or seals, they shall be examined and maintained to prevent excessive loss of fluid. 8.6.5.5.1 Jack assembly on right side looking into the hoistway shall be repacked. Ref: (G)1
|
11/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1)
|
11/8/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.2 Callbacks (Trouble Calls) Documentation
|
|
|
2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2
|
11/8/2020
|