Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) 1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x 1) Emergency operation of signaling devices, lighting, communication and ventilation, shall be maintained. Emergency phone is not functioning. Ref: 8.6.4.15 10/8/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 1. All machine rooms or enclosures shall have a self-closing and self-locking door. The door to machine room won't close, either door or jamb swollen up possible from moisture. 12/6/2018
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.2 Callbacks (Trouble Calls) Documentation 2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2
MO Minimum : Elevators (K) - Car Platforms and Car Slings (K)4 2. All elevators shall have data plates attached to the crosshead. Could not find data plate on the crosshead. 12/6/2018
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone line is not working. Re-inspection required 3/3/2024