Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Only one fluorescent fixture bulb is working in the car. Provide at least two bulbs with a minimum of five foot candles of light in the car.
MO Minimum : Elevators (H) - Machine Rooms (H)2 Need to provide a self locking machine room door, operable from the inside with a key
MO Minimum : Elevators (H) - Machine Rooms (H)3 Repair the elevator machine room ceiling. 5/3/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove all non-elevator equipment from the machine room. 5/3/2019
MO Minimum : Elevators (I) - Pits (I)5 Provide a permanent means to remove the water from the elevator pit. 5/3/2019
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a noncombustible cover that is flush with the pit floor. There is currently no cover provided.
MO Minimum : Elevators (I) - Pits (I)8 The sump pump hole in the pit shall be provided with a noncombustible cover that is flush with the pit floor. There is currently grating or cover. Second notice.