Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection incomplete, elevator ceased operation during testing. Need to perform the following tests to complete inspection: all fire service, pit equipment and get slide measurement. Re-inspection required 4/17/2025
MO Minimum : Elevators (F) - Electrical Switches (F)2 x x Top final limit switch was not actuated before counterweights compressed buffer. Red-tagged, Re-inspection required 4/17/2025
MO Minimum : Elevators (F) - Electrical Switches (F)2 x x Bottom final limit switch activates just as car compresses buffer. Red-tagged, Re-inspection required 4/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall work on backup power and be answered 24/7. Re-inspection required 4/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car shall work for more than 3 seconds. Re-inspection required 4/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car shall work for more than 3 seconds. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.3.5 x An emergency power test with 125% capacity shall be performed and witnessed. 12/2/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Provide testing of Phase I operations, record results. 7/12/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Provide testing of Phase II operations, record results. 7/12/2023
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 x Check door force. 7/12/2023
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 8.6.4.20.1 x Provide Cat 1 testing of car safeties, check slide..Car stopped running. 7/12/2023