ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.3.5
|
x
|
|
An emergency power test with 125% capacity shall be performed and witnessed.
|
12/2/2020
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
x
|
Bottom final limit switch activates just as car compresses buffer. Red-tagged, Re-inspection required
|
4/17/2025
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.6.4.19.8
|
x
|
|
Check door force.
|
7/12/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car shall work for more than 3 seconds. Re-inspection required
|
4/17/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car shall work for more than 3 seconds. Re-inspection required
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work on backup power and be answered 24/7. Re-inspection required
|
4/17/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection incomplete, elevator ceased operation during testing. Need to perform the following tests to complete inspection: all fire service, pit equipment and get slide measurement. Re-inspection required
|
4/17/2025
|
A17.1-2016 : Elevators
|
2.29 - Car and counterweight safeties
|
8.6.4.20.1
|
x
|
|
Provide Cat 1 testing of car safeties, check slide..Car stopped running.
|
7/12/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Provide testing of Phase I operations, record results.
|
7/12/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
|
Provide testing of Phase II operations, record results.
|
7/12/2023
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
x
|
Top final limit switch was not actuated before counterweights compressed buffer. Red-tagged, Re-inspection required
|
4/17/2025
|