Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be posted in the elevator machine room. 9/18/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 9/18/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams The controller shall not have jumpers on relays. 9/18/2020
MO Minimum : Elevators (A) - Hoistways (A)12 The hole in the front hoistway wall at the second landing shall be patched using approved solid material. 6/16/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 The emergency exit must be fastened from the top and have the ability to be opened without the use of tools. 6/16/2021
MO Minimum : Elevators (I) - Pits (I)1 Debris shall be removed from the pit. 6/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 6/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher is expired. A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 6/21/2022
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Remove the debris from pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. The fire service log in the MCP does not identify the persons performing the test.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The car shall not respond to car call demand when on fire service phase two hold operation. 12/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency telephone shall be operational. 6/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The in car emergency lighting shall be operational. 6/22/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x On Phase 2 fire service, the hold function does not work. 6/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency light and alarm bell shall be operational. 10/19/2022