MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers.
|
1/24/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing and shall be operable from the interior space without the use of a key.The closing mechanism has been removed.
|
1/24/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Fire jewel and buzzer are not working on fire recall. Reinspect within 30 days.
|
1/28/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
The fireman's emergency service phase I operation was tested and the following deficiency was noted: The visual or audio signal device did not activate in the car when phase I was activated.
|
12/7/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
|
|
The fireman's emergency service phase I operation was tested and the following deficiency was noted: The visual or audio signal device did not activate in the car when phase I was activated.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
1/24/2023
|