Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide self locking mechanism for machine room door. 8/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Label main line disconnect feed source, panel and breaker. 2.8 8/3/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Label 110VAC car light disconnect feed source, panel and breaker. 2.8 8/3/2022
MO Minimum : Elevators (H) - Machine Rooms (H)8 Fire recall module in machine room missing cover. 8/3/2022
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 OSV valve not tested at time of inspection. Reinspection required for certificate. 11/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger pump from elevator pit. 11/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide self locking mechanism for machine room door. 11/28/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Provide feed source for main line disconnect. 11/28/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) Provide feed source for 110V car light disconnect. 11/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)8 Fire recall module in machine room missing cover. 11/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Provide pit container for oil collection in pit not to exceed 5 gallon capacity. 11/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Remove padlock from machine room door, and provide a self locking mechanism for machine room door. 7/8/2024