Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Emergency light and bell do not operate. 7/8/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine room 3/2/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove oil and debris from machine room floor. 3/2/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 Replace or repair hydraulic pumping unit that is leaking oil onto machine room floor. 3/2/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current state operating certificate inside the machine room 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Wiring diagrams shall be kept in the machine room 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to corridor call station at each landing 4/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Test and log firefighter operation monthly 4/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No machine room lighting. Repair or replace light fixture.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency bell does not operate 11/26/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting burned out
MO Minimum : Elevators (H) - Machine Rooms (H)1 KEEP MACHINE ROOM ACCESSABLE ( BUILDING IS STORING EQUIPMENT IN FRONT OF MACHINE ROON DOOR )