Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Emergency light in cab does not work. 1.5 9/10/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Alarm bell in cab does not work. 1.6 6/24/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Phone in cab does not work. 1.6 6/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not work - no power to line. 8/26/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Elevator cab emergency lights do not work. Re-inspection required
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure x Emergency phone shall work. 10/30/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase II key switch would not turn during the fire service test. Repair or replace phase II key switch and test phase II fire service. Re-inspection required