MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Hoistway door interlocks must be maintained. Floor 2 hoistway door interlock breaks electrically while still being locked mechanically.
|
3/28/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
Repair or replace GFI in machine room.
|
10/7/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Firefighters' Service test was not performed.
|
4/29/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Emergency power is existing, but not tested.
|
4/29/2021
|
A17.1-2016 : Elevators
|
3.14 - Hoistway clearances
|
8.11.3.1.3(o)
|
|
|
Car door equipment clipping hoistway door equipment on some floors.
|
6/4/2024
|
conversion
|
conversion
|
n/a
|
|
|
Observed car emergency light not working.
|
10/7/2020
|