Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)3 No No Hoistway door interlocks must be maintained. Floor 2 hoistway door interlock breaks electrically while still being locked mechanically. 3/28/2023
MO Minimum : Elevators (H) - Machine Rooms (H)7 No No Repair or replace GFI in machine room. 10/7/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Firefighters' Service test was not performed. 4/29/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Emergency power is existing, but not tested. 4/29/2021
A17.1-2016 : Elevators 3.14 - Hoistway clearances 8.11.3.1.3(o) No No Car door equipment clipping hoistway door equipment on some floors. 6/4/2024
conversion conversion n/a No No Observed car emergency light not working. 10/7/2020