MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A current MCP and related maintenance records, including fire service log, shall be on-site.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
11/3/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
Hoistway door safety retainers missing on all floors.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP, including PM records and monthly fire service log, not being properly documented.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Provide a code compliant pit ladder. Current ladder does not comply with Missouri Minimums.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
x
|
|
Provide a fire extinguisher in the elevator machine room mounted in a readily accessible location.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
x
|
|
Provide code compliant pit lighting, measured at 7 ftc.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Provide feeder location on 110v disconnect.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Provide feeder location on main line disconnect.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
Provide GFCI type receptacle in the elevator machine room.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Provide means to reset GFCI receptacle in the pit.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.11.2.1.1(o)
|
x
|
|
Provide missing lobby warning placard on 6th floor.
|
3/11/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Remainder of inspection shall be completed: Remaining category 5 testing/annual items: Car and counterweight buffers, door pressure, final limit switch, and governor pull out/pull thru.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
8.11.2.1.3(p)
|
x
|
|
Seal all holes and penetrations in the hoistway.
|
3/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
2.20
|
|
|
Suspension rope tail ends shall be properly seized/banded. (Currently just electrical taped, multiple ends missing)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
There are fire gibs missing from the hoistway doors.
|
8/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13
|
x
|
|
There are fire gibs missing from the hoistway doors. (2nd Notice)
|
9/19/2023
|