Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform pressure relief test 10/15/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform annnual pressure relief test 9/20/2022
MO Minimum : Elevators (F) - Electrical Switches (F)6 x Top of car emergency exit switch does not open when emergency exit is opened 9/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 11/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light and emergency alarm button are pushed inside car operating panel and meed to be reattached to the car panel 9/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency phone does not operate 10/15/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) THE PIT LIGHT SWITCH SHALL BE LOCATED TO BE ACCESSIBLE FROM THE PIT ACCESS DOOR. 10/17/2024
conversion conversion n/a Pit light switch does not operate pit light. Duct is blocking pit light switch. 10/28/2019
conversion conversion n/a Emergency light and bell do not operate 10/28/2019
conversion conversion n/a Provide code data plate for code in effect at time of alteration, and at time of installation. 10/28/2019