Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emergency light and bell do not operate. 12/3/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No Need to post fire service instructions inside the elevator 12/3/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Replace rouged and undersized governor rope. 7/16/2021
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 Yes Yes Car safeties do not stop the elevator. Slide is 56 inches and exceeds allowed limits 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2.5 Rope Tension (Re-Inspect) Yes No Equalize hoist rope tension 12/8/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Lobby dial position indicator is not operating and needs repair. 12/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No Install seal on machine brake spring tension adjustment nut. 7/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace worn traction sheave liners 12/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace broken hoist rope shackle springs on the car and counterweight connections 12/7/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Need to remove debris from machine room floor. 8/25/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Need to post emergency evacuation of passengers form inside machine room. 8/25/2020