Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x x Door close button does not work on Phase II. Red tagged elevator until repaired. 2/1/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Expired
MO Minimum : Elevators (I) - Pits (I)5 Install pit ladder.
MO Minimum : Elevators (I) - Pits (I)5 Install pit ladder.
MO Minimum : Elevators (I) - Pits (I)5 Install pit ladder.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No current certificate on display. 9/19/2023
MO Minimum : Elevators (I) - Pits (I)5 No means to access pit.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide 24/7 monitoring. Currently goes to front desk.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Provide code complaint means to collect oil in the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger return line.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Remove scavenger unit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Seals and glands cannot be monitored for oil loss if there is an automatic system to pump hydraulic fluid back to reservoir.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Seats and glands cannot be monitored for oil loss if there is an automatic system to pump hydraulic fluid back to reservoir.