Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone in cab does not work. Re-inspection required 11/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The battery back–up lowering device was tested and did not operate as designed, the elevator failed to return to a lower floor and open its doors. Repair the device to operate as it is designed. 9/20/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The elevator pit light fixture did not work on the day of inspection, repair for proper illumination of the pit floor. 9/20/2021
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x The hydraulic pressure switch operation, on the elevator controller will not perform as required when the oil pressure was decreased. The pressure switch operation shall be repaired to operate as required. Re-inspection required 11/30/2023
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 (Re-Inspection) x The hydraulic pressure switch operation, on the elevator controller, will not perform as required when the oil pressure was decreased. The pressure switch operation shall be repaired to operate as required. 10/10/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-Way communication is inoperable, and shall be repaired or replaced. Reinspection required.