MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need In Case of Fire signs by each Hall call button 5/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Need Phase I Fire service instructions 5/14/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in Elevator equipment room overdue inspection 5/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Water lines running over elevator controller need to be guttered or controller needs to be protected in some other way to prevent water damage if there is a leak 5/14/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No machine room lighting. Ceiling fixture is in extreme dis-repair. 6/22/2023