Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide type ABC fire extinguisher inside machine room next to access door. 11/3/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing. 11/3/2020
MO Minimum : Elevators (H) - Machine Rooms (H)4 Remove non-elevator related material from machine room. 11/3/2020
MO Minimum : Elevators (I) - Pits (I)1 Remove oil from pit floor 11/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not illuminate 10/17/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door shall be self-locking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing
MO Minimum : Elevators (A) - Hoistways (A)13 Seal hole that penetrates hoistway wall at lobby landing.
MO Minimum : Elevators (A) - Hoistways (A)16 Remove exposed non-elevator related wiring from the hoistway enclosure.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light does not operate 10/11/2024
MO Minimum : Elevators (A) - Hoistways (A)16 Remove non-elevator related wiring from the hoistway
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to hall button fixture at each landing