MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
No
|
No
|
Need maintenance control program on site posted on controller
|
10/27/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
No
|
No
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/10/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone shall be operational.
|
5/8/2025
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
Yes
|
No
|
Replace hoist ropes (red rouge (reduced diameter)
|
1/14/2020
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
No
|
No
|
Provide monthly fire service testing of fire service and document on log in machine room
|
1/14/2019
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency/standby power operation of the elevator shall be tested.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Test emergency power. Elevator did not work per code requirements.
|
7/20/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency power operation of the elevator needs to be tested.
|
11/21/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Need all CAT5 components of testing.
|
5/28/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Emergency power operation of the elevator shall be tested.
|
5/24/2024
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
Yes
|
No
|
Lighting in the machine room shall be not less than ten (10) foot-candles at floor level.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
7/19/2024
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
No
|
No
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
7/19/2024
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(d)(1)
|
No
|
No
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
7/19/2024
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
Yes
|
No
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
Yes
|
No
|
A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2(d)(1)
|
Yes
|
No
|
Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.3
|
Yes
|
No
|
Where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
Yes
|
No
|
All live parts of electrical apparatus in the hoistway and the machine room shall be enclosed.
|
8/11/2021
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
No
|
No
|
Adjust upthrust roller bearings for proper clearance to door hanger track such that the door-to-door gap at the bottom is less than 1".(All floors)
|
5/28/2026
|
|
A17.1-2016 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
No
|
No
|
2.21.1.3.1 Replace cracked/dry-rotted lower Counterweight Rollers.
|
5/28/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
Pit shall be kept clean. Remove excess debris and fan.
|
5/28/2026
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
Yes
|
No
|
Hoist ropes have stretched and the counterweight is compressing the buffer.
|
7/20/2023
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.5 Illuminated Visual Signal
|
Yes
|
No
|
Phase I Recall illuminated Fire Hat at Main landing is not working.
|
5/28/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection)
|
Yes
|
No
|
The emergency stop switch in the car shall not be made ineffective on Phase I emergency Recall Operation.
|
5/28/2026
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/10/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Up to date operating certificate required in the elevator machine room.
|
6/24/2024
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/24/2024
|