MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
12/22/20: 2-way communication device shall work and give proper location
|
3/10/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
12/22/20: 2-way communication device shall work and give proper location
|
3/10/2022
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)2
|
x
|
|
12/22/20: Replace damaged limit switch rollers.
|
3/10/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
12/22/20: Battery Lowering shall work. Repair or replace.
|
5/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair cab stabilizer
|
5/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
12/22/20: Emergency/auxiliary lighting shall work with power loss.
|
3/10/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
12/22/20: Emergency/auxiliary lighting shall work with power loss.
|
3/10/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly.
|
5/23/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
12/22/20: MCP shall be kept in equipment room,and Fire service testing log, recorded monthly. No MCP present
|
5/23/2022
|