Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 12/22/20: 2-way communication device shall work and give proper location 3/10/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x 12/22/20: 2-way communication device shall work and give proper location 3/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x 12/22/20: Emergency/auxiliary lighting shall work with power loss. 3/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x 12/22/20: Emergency/auxiliary lighting shall work with power loss. 3/10/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A17.1-2016:8.6.1.4 :Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil loss log and Fire service testing log, recorded monthly. 5/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1) Repair damaged car riding lanterns (direction arrows) 5/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1). Battery Lowering shall work. Repair or replace. 5/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records G(1)/8.6.1.4 : MCP shall be kept in equipment room, and Fire service testing log, recorded monthly. 5/23/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed x x REDTAG. PISTON PACKING BLOWOUT DURING TEST. REPAIR AS NEEDED. REINSPECT TO RETURN TO SERVICE (“Stop ring test”) 5/20/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed x REDTAG. PISTON PACKING BLOWOUT DURING TEST. REPAIR AS NEEDED. REINSPECT TO RETURN TO SERVICE (“Stop ring test”) 5/20/2022
MO Minimum : Elevators (F) - Electrical Switches (F)2 x Replace damaged limit switch rollers. 5/20/2022
MO Minimum : Elevators (F) - Electrical Switches (F)2 x Replace damaged limit switch rollers. 5/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Replace missing fishplate bolt. 5/23/2022