Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 New door reopening device installed and improperly wired per NFPA 70. Reopening device is wired to car lighting branch circuit. 10/9/2018
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing. 11/17/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x Smoke sensitive door reopening device not disabled on phase 1 firefighters operation. 11/17/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room access door needs to be self-closing and self-locking 6/21/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Post In Case of Fire signage next to corridor call station at each landing 6/21/2022