Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A18.1-2005 : Lifts & Chairlifts 2.11 - Emergency Signals 2.11.2 x Emergency phone does not work. 10/14/2024
ASME A18.1-2005 : Lifts & Chairlifts 2.8 - Safeties and Speed Governors 2.8 x Unit is overdue for category 5 test. State database indicates last tested in 2018. Customer shall provide proof of category 5 testing within last 5 years or testing is due now. 10/14/2024
ASME A18.1-2005 : Lifts & Chairlifts 11 CSR 40-5.090 Inspection and Testing 10 Routine, Periodic, and Acceptance inspections andTest x Incomplete unit had a mechanical faliure. Stop ring, top limits, slack cable switches, and slack cable jaws remain to be tested.
ASME A18.1-2005 : Lifts & Chairlifts 3.11 - Emergency Signal 3.11 x Emergency phone shall work with loss of main 120v power.
Missouri Minimum : Platform Lifts (U) - Existing Vertical and Inclined Platform Lifts (U)1 (Re-Inspect) x Emergency phone in platform lift is not working, needs repair. Re-inspection required 3/7/2023