Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.36 - Hydraulic Cylinders 1004.2(b)(19) Scavenger pumps are no longer allowed. Replace with other collection means. 12/17/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide MCP 4/4/2022
MO Minimum : Elevators (I) - Pits (I)1 Oil in sump hole,remove. Determine if sump pump works,replace if needed. 4/4/2022
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Unsealed. 4/4/2022
MO Minimum : Elevators (S) - Fire Service 211.8 Switch Keys Provide, leave in elevator machine room. 4/4/2022