MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
1/3/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
6/30/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
6/30/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit floor is covered with at least 1/2" of oil, and oil is covering the head. Clean up all oil.
|
6/30/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Plunger/cylinder packing is worn and leaking and shall be repair or replaced as needed.
|
7/13/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.3.2.2 Cylinders Test shall be performed
|
x
|
|
Plunger/cylinder packing is worn and leaking and shall be repair or replaced as needed.
|
6/9/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
1/3/2022
|