Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Plunger/cylinder packing is worn and leaking and shall be repair or replaced as needed. 7/13/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 6/30/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit floor is covered with at least 1/2" of oil, and oil is covering the head. Clean up all oil. 6/30/2020
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 6/30/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 1/3/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed x Plunger/cylinder packing is worn and leaking and shall be repair or replaced as needed. 6/9/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 1/3/2022