MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning)
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
1/3/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Battery lowering operation shall be functional.
|
6/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.3.2.2 Cylinders Test shall be performed
|
x
|
|
Car failed to maintain floor level during 15 minute stand test. It was determined to be leaking back through the valve. Repair or replace valve. Perform 15 minute standing test and re-establish a working pressure.
|
6/9/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
8.6.1.7.5 - The emergency lowering device (ERU) shall be operational.
|
2/17/2021
|