Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ICC A117.1-2009 407.2 - Elevator Landing Requirements 407.2.1.3 Yes No Security Card access sensors obstruct clear access to both hall stations. Relocate.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Elevators that operate on emergency power shall be tested. Hall station EP jewel shall be added.
ICC A117.1-2009 407.2 - Elevator Landing Requirements 407.2.1.3 Yes No Security Card access sensors obstruct clear access to both hall stations. Relocate. 6/19/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Emergency battery back up lowering unit is inoperable. Repair or replace. Reinspection required 12/19/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No 1.6 Test Em Light/Alarm/phone. Unable to test due to lighting issue. 1/5/2026
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.3 Yes No Pit Sprinkler shall not be more than 24" from Heat Detector and not more than 24" from pit floor. Relocated Sprinkler head to approved location. 1/5/2026
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.10.2.2.1(e) Yes No Cab Lighting shall work. (previous lighting shorted and to be replaced) 1/5/2026
A17.1-2016 : Elevators 1.8 - Door closing force 8.10.2.2.1(h) Yes No Test Door Closing Force 1/5/2026
A17.1-2016 : Elevators 1.14 - Ventilation 8.10.2.2.1(n) Yes No Test Cab fan operation. 1/5/2026
A17.1-2016 : Elevators 2.14 - Code data plate 8.10.2.2.2(ll) Yes No Controller needs Alteration Code Data Plate. 1/5/2026
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 8.10.2.2.2(m) Yes No Controller needs knockout hole cover. 1/5/2026
A17.1-2016 : Elevators 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) 8.6.11.1 Firefighters’ Emergency Operation Yes No Test Phase 1 & 2 along with Car Stop switch bypass. 1/5/2026
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No Car door shall be restricted to not more than 4" open. Adjust bracket @ 1. 1/5/2026
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No Test Communication Loss System 1/5/2026