A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
Yes
|
No
|
Emergency battery back up lowering unit is inoperable. Repair or replace. Reinspection required
|
12/19/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.19.15 Emergency Communications
|
Yes
|
No
|
Test Communication Loss System
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
8.6.4.13.1(l)(Door Restrictor)
|
Yes
|
No
|
Car door shall be restricted to not more than 4" open. Adjust bracket @ 1.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980)
|
8.6.11.1 Firefighters’ Emergency Operation
|
Yes
|
No
|
Test Phase 1 & 2 along with Car Stop switch bypass.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
Yes
|
No
|
Elevators that operate on emergency power shall be tested. Hall station EP jewel shall be added.
|
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.10.2.2.2(m)
|
Yes
|
No
|
Controller needs knockout hole cover.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
2.14 - Code data plate
|
8.10.2.2.2(ll)
|
Yes
|
No
|
Controller needs Alteration Code Data Plate.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.14 - Ventilation
|
8.10.2.2.1(n)
|
Yes
|
No
|
Test Cab fan operation.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.8 - Door closing force
|
8.10.2.2.1(h)
|
Yes
|
No
|
Test Door Closing Force
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.10.2.2.1(e)
|
Yes
|
No
|
Cab Lighting shall work. (previous lighting shorted and to be replaced)
|
1/5/2026
|
|
ICC A117.1-2009
|
407.2 - Elevator Landing Requirements
|
407.2.1.3
|
Yes
|
No
|
Security Card access sensors obstruct clear access to both hall stations. Relocate.
|
6/19/2025
|
|
ICC A117.1-2009
|
407.2 - Elevator Landing Requirements
|
407.2.1.3
|
Yes
|
No
|
Security Card access sensors obstruct clear access to both hall stations. Relocate.
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.3
|
Yes
|
No
|
Pit Sprinkler shall not be more than 24" from Heat Detector and not more than 24" from pit floor. Relocated Sprinkler head to approved location.
|
1/5/2026
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
1.6 Test Em Light/Alarm/phone. Unable to test due to lighting issue.
|
1/5/2026
|