MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
1/22/2019
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
|
|
Provide a permanent means to access machine room.
|
1/22/2019
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Post capacity plate and "No Passengers" signage inside elevator cab.
|
1/22/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)7
|
|
|
Provide a pit stop switch.
|
1/22/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Provide code compliant pit lighting.
|
1/22/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Adjust the gate switch to prevent the car from running when the car door is open greater than 2".
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Adjust the top floor door for proper balance.
|
11/4/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Adjust the top floor door locking bar for proper operation.
|
11/4/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
|
9/8/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The lighting in the machine room shall be not less than 10 foot-candles at floor level.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/1/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Install a code data plate. It shall read: "Missouri Minimums"
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/1/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The reverse phase switch is broken and requires replacement.
|
7/16/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
9/1/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
|
|
The four inch electrical box located in the machine room requires a cover.
|
9/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit of dirt and debris.
|
9/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than 5 foot-candles at the pit floor. The fixture switch shall be provided and accessible from the pit access door.
|
9/1/2021
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
|
|
Each freight car enclosure shall have lighting not less than two and one-half (2.5) foot-candles. Bulbs or tubes shall be guarded to prevent breakage.
|
9/1/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)3
|
|
|
Counterweight guards shall extend from a point not more than 12" above the pit floor to a point not less than 7' above the pit floor.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The electrical box attached to the underside of the car needs a cover plate.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
The in car emergency lighting shall be operational.
|
7/16/2021
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)1
|
|
|
There is structural damage under the car frame that shall be repaired.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The electrical box attached to the top of the car needs a cover plate.
|
9/1/2021
|
MO Minimum : Elevators
|
(M) - Car Safeties and Speed Governors
|
(M)6
|
x
|
x
|
Remove the unwired governor speed switch. Governor speed switch is not required for elevators running less than 150 fpm. - Unit not Red Tagged
|
7/16/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
|
9/8/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/1/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device.
|
9/1/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/19/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be operational.
|
9/19/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
9/19/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
The vision panel on the first floor does not meet code. The vision panel in the basement is broken. Replace both panels to meet the following code: Ref: A17.1-2016, 2.14.2.5, A17.2, 1.11
|
9/16/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
x
|
This car has been red tagged. Upon arrival, the button was pushed to call the elevator, the doors opened, and the car was not at the floor.
|
8/31/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
There is a 3 1/2" gap between the door and the wall; it should be around 1 1/4".
|
8/31/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing is complete. Need to do all of the annual, slide, pull out/pull thru, and governor switch.
|
8/31/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
There is a 3 1/2" gap between the door and the wall; it should be around 1 1/4". Take corrective action.
|
8/26/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Testing is incomplete. Need to do all of the annual, slide, pull out/pull thru, and governor switch.
|
8/26/2024
|