A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
1001.2(d)(2)
|
|
|
The hoistway door tension on the bottom landing shall be adjusted to self-close.
|
10/31/2019
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
x
|
|
The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor.
|
9/5/2019
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
The counterweight is close to touching the spring buffer when the elevator travels to the top floor. The hoist ropes shall be shortened to provide a minimum run-by of 6 inches. Reinspection required in 30 days.
|
10/20/2022
|