Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required.
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x The counterweight is close to touching the spring buffer when the elevator travels to the top floor. The hoist ropes shall be shortened to provide a minimum run-by of 6 inches. Reinspection required in 30 days. 10/20/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 x The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 9/5/2019
A17.1-1996 : Elevators 4.2 - Hoistway doors 1001.2(d)(2) The hoistway door tension on the bottom landing shall be adjusted to self-close. 10/31/2019