Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 9/17/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Elevator cab phone does not work, needs repaired. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Elevator can door restrictor does not work, needs repaired. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A written copy of the MCP shall be kept in the machine room for each unit
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test elevator for operation on emergency power. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The audible signal device did not sound when phase I was activated. 10/11/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x A17.2 6.4 Elevator was out of service when phase I and II Fireman’s Service was tested. 9/17/2025
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in dust and debris. The pit shall be cleaned. 9/17/2025