MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water, the elevator pit shall be kept clean and dry. A sump pump may be required if this condition is reoccurring.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. A sump pump shall be added to prevent the accumulation of water. The sump pump shall comply with all state and county requirements.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry.
|
10/31/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry. A sump pump shall be added to prevent the accumulation of water. The sump pump shall comply with all state and county requirements.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
There is a pipe that carries liquids directly above the elevator drive motor and controller. This pipes shall be guttered to assure that no discharge from this pipe falls onto the elevator equipment.
|
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
x
|
|
Winding drum operated machines shall have the hoist ropes reshackeled every two year, reshackling of this unit is overdue. Reinspection is required.
|
|