Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The ADA telephone inside the elevator is programmed to be answered by 911 non-emergency dispatch center resulting in a 15 minute delay in establishing communication. While this is not a code violation, the operator at 911 is not trained to answer this phone for two-way communication which is a code violation. To avoid nuisance calls and possible billing for emergency services, correct the programming of this phone to be answered by a monitoring service that is capable of notifying the proper personnel and answering the phone in a timely manner. Your service company is currently Thyssenkrupp Elevator, who does have a service available or a building alarm company.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Hold position on Phase II fire service does not work, front and rear doors. 11/13/2019
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Emergency battery lowering device is not working, needs repaired. Re-inspection required 9/25/2024