Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/31/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 11/20/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Up-to-date operating certificate is required in the machine room. 11/20/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be completed and documented monthly. The form is present in the MCP, but has not been logged monthly. 4/6/2026