Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The bottom floor hall button shall be properly fastened to the wall. 12/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Capacity plate shall be installed in the car. 12/2/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 2/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Phone door is missing appropriate handle. 2/10/2026
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and free of oil and debris. Pit floor covered in oil, sump hole full of oil. Clean excessive oil, investigate and repair cause. 2/10/2026
MO Minimum : Elevators (S) - Fire Service (S)1 x x Repair Phase 1 Fire Service Audio Alarm in car 4/24/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Improper controller fusing. There is a 10A fuse in a 6A circuit. Replace with correct fuse. 2/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/3/2022