A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No Maintenance Control Program Documentation on-site
|
2/14/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
No instructions to locate maintenance records posted
|
2/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Per memorandum 008(b) MCP records required on site
|
5/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Per memorandum 008(b) FFS log required on site
|
5/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
x
|
|
car has 28' toe guards elev has rope gripper needs 48" toe guards
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
top an bottom access sws. not working properly
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
less than 6" between counterweight an spring buffer
|
3/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.3.3.3 Runby & Clearances After Reroping or shortening
|
x
|
|
less than 6' runby
|
3/9/2020
|