ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Per memorandum 008(b) MCP required on site
|
5/3/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.11.1
|
|
|
Per memorandum 008(b) FFS log required on site
|
5/3/2021
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
No Maintenance Control Program Documentation on-site.
|
2/14/2022
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4 Instructions for Locating Maintenance Records
|
|
|
No instructions for locating maintenance records provided.
|
2/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
8.6.1.6.7
|
|
|
phase one fire serv bezel in hall not readable
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
|
|
phone verifacation not working
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
|
|
car has 28" toe guards has rope gripper need 48 " toe guards
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
8.6.3
|
x
|
|
no anti spin cable thru shackles
|
3/9/2020
|