A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)12
|
x
|
x
|
Phase 2 fire service shall be operational. Fixed 4/17/2020 - Re-Inspect set for 5/28/2020 - 7AM
|
5/28/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
The in car emergency light shall be operational.
|
5/28/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The alarm bell shall be operational on auxiliary power.
|
5/28/2020
|
A17.1-2016 : Elevators
|
5.15 - Overspeed Valve
|
8.6.5.16.5
|
|
|
Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
x
|
x
|
8.6.5.14.2 During the standing test, the elevator seeped down 4" in 2 minutes. Identify and correct the source of oil loss before the elevator can returned to service.
|
|